9780
Pipe burst safety valve Cla-Val
including flow diaphragm, manometer and optical display
Diameter range DN 32 (1 1/4") – DN 1400
Pressure rating PN 10 I PN 16 I PN 25 I PN 40
- The Cla-Val pipe protection valve is equipped with a measuring orifice on the input side.
- If the flow reaches the specified pipe breakage volume and thus the specified differential pressure, the valve closes.
- Once the pipe breakage has been remedied, the pipe protection valve must be put back into operation.
- Minimum input pressure 0.2 bar, minimum differential pressure 0.5 bar.
- Orifice plate differential pressure 0.3 bar.
Hawle quality guarantee

Product variants (1)
Bookmark | BIM data | Item number | Description | Nominal diameter | Pressure rating | Weight |
---|---|---|---|---|---|---|
5014768 | PIPE BURST SAFETY SHUT-OFF VALVE PN16 |
DN 50 | PN16 | 17 KG |
Downloads